Reserved GPU capacity

GB300 NVL72 specs: power, cooling and memory

Blackwell Ultra rack, 72 GPUs · Updated 20 October 2026
By , Co-Founder of Ancapex

A GB300 NVL72 rack holds 72 Blackwell Ultra GPUs and 36 Grace CPUs in 18 compute trays, joined by 9 NVLink switch trays into one 130 TB/s NVLink domain, with 20 TB of HBM3e (NVIDIA). Server makers rate the rack at about 132 to 135 kW, up to 155 kW at peak, with about 90% of the heat removed by liquid.

GB300 NVL72 is NVIDIA's Blackwell Ultra rack: one 48U rack that works as a single 72-GPU system. It is bought and rented as a whole rack. Every figure below links to its source.

Book a call → Send a request

The rack

SpecGB300 NVL72Source
GPUs and CPUs72 Blackwell Ultra GPUs, 36 Grace CPUs (2,592 Arm Neoverse V2 cores)NVIDIA GB300 NVL72
Trays18 compute trays of 2 Grace CPUs and 4 GPUs; 9 NVLink switch traysDGX GB200/GB300 user guide
GPU memory20 TB HBM3e, up to 576 TB/s; 21 TB in Supermicro's sheetNVIDIA GB300 NVL72, Supermicro
CPU memory17 TB LPDDR5X, 14 TB/sNVIDIA GB300 NVL72
NVLink130 TB/sNVIDIA GB300 NVL72
FP4 Tensor1,080 dense, 1,440 sparse (petaFLOPS)NVIDIA GB300 NVL72, NVIDIA DGX GB300
FP8 / FP6 Tensor720 sparse (petaFLOPS)NVIDIA GB300 NVL72
FP64100 TFLOPSNVIDIA GB300 NVL72
Networking800 Gb/s per GPU through ConnectX-8, Quantum-X800 InfiniBand or Spectrum-X EthernetNVIDIA GB300 NVL72

The GPU

SpecBlackwell Ultra in GB300Source
Memory279 GB HBM3e at 8 TB/s in NVIDIA's datasheet; 288 GB in NVIDIA's technical blog and OEM sheetsBlackwell Ultra datasheet, NVIDIA technical blog, Supermicro
PowerConfigurable up to 1,400 W (Lenovo lists 1,100 W)Blackwell Ultra datasheet, Lenovo Press
FP4 Tensor15 dense, 20 sparse (petaFLOPS)Blackwell Ultra datasheet
NVLink1.8 TB/sBlackwell Ultra datasheet

Power

SourceRack power
SupermicroEight 1U power shelves of 33 kW (six 5.5 kW supplies each), 132 kW of total power
Lenovo Press135 kW TDP, up to 155 kW at peak; six or eight 33 kW power shelves
DGX GB200/GB300 user guideAbout 120 kW for a DGX GB rack; eight power shelves with N+N redundancy turn AC into 50 to 51 V DC on the busbar

NVIDIA added energy storage to the GB300 NVL72 power shelves, 65 joules per GPU, which cut the peak power the grid sees by 30% in its Megatron training test (NVIDIA power blog).

Cooling and the rack itself

Dates

Renting GB300 NVL72

In our offers GB300 NVL72 racks can start from Q1 2027, usually on terms of 3 to 5 years. See GB300 NVL72 rental, what a rack costs to buy and B300 vs GB300 NVL72.

FAQ

How much power does a GB300 NVL72 rack use?

About 132 to 135 kW by server makers' ratings: Supermicro 132 kW, Lenovo 135 kW and up to 155 kW at peak.

How many power shelves does GB300 NVL72 have?

Eight 1U shelves of 33 kW, each with six 5.5 kW supplies, in Supermicro's and NVIDIA's descriptions; NVIDIA describes them as N+N redundant, and Lenovo offers six or eight.

How much memory does GB300 NVL72 have?

20 TB of HBM3e for the 72 GPUs and 17 TB of LPDDR5X for the 36 Grace CPUs in NVIDIA's figures.

Is GB300 NVL72 liquid-cooled?

Yes: NVIDIA calls it fully liquid-cooled; its SuperPOD document says GPUs and CPUs are liquid-cooled and other parts air-cooled, and about 90% of the rack's heat goes to liquid in Lenovo's figures.

How much does a GB300 NVL72 rack weigh?

We found no full-rack weight published by NVIDIA, Supermicro or Lenovo; Lenovo gives 185 kg for the empty rack, 29 kg per compute tray and 17 kg per switch tray.